 Arc-Fault Circuit Interrupter (AFCI) Circuit Breaker
Siemens 20A AFCI Siemens Combination Type AFCI trip indicators provide a valuable analysis tool to help electricians pinpoint the type of trip. These indicators are in the form of LEDs that appear near the handle of the breaker. The LED indicators will appear for 5 seconds each time the AFCI is turned “ON” up to 30 days after the last trip. One LED will be illuminated if the last trip was a result of an arcing fault to ground. No indicator will be displayed if the AFCI trips as a result of an overcurrent condition. The last known trip indicator can also be manually cleared from memory to assist with verifying resolution of the problem.

LED Indication Guide (after recent trip has occurred)
Turn AFCI to "ON" position. Observer LED indications and compare to chart below.
LED indications will appear for 5 seconds each time the AFCI is turned "ON". Display will appear each time the AFCI is reset up to 30 days after last trip.

 LED Indicator
 Last Known Trip Condition
 LED(A)  LED(B)  
 OFF  OFF  Overcurrent
 ON  OFF  Arc Fault
 ON  ON  Arc Fault to Ground